FAQ – Preventing flash vapour in condensate

How can flash vapour formation be prevented in a heat recovery system?

What is flash steam?

The term ‘flash steam’, also known as ‘re-vapourisation steam’, refers to the steam formed when hot condensate undergoes a drop in pressure.

Flash steam is no different from live steam. This term simply refers to the method by which the steam is produced. Steam systems normally produce live steam using a boiler, a steam generator or a heat recovery generator. Flash steam is produced when high-temperature, high-pressure condensate undergoes a sharp drop in pressure, such as at the outlet of a steam trap.

High-temperature condensate contains a great deal of energy. When there is a drop in pressure, the condensate cannot remain entirely in its liquid form because it contains more energy than saturated water can hold at that pressure. A certain percentage of the condensate therefore flashes into vapour to release some of that energy.

To limit the formation of flash steam in a thermal plant, it is necessary to control the conditions under which hot condensate undergoes a pressure drop. There are two possible approaches: lowering its temperature prior to expansion, using a subcooling heat exchanger, or maintaining a return pressure compatible with its temperature.

The first solution offers particular energy benefits. Instead of allowing the condensate to re-evaporate at the outlet of the circuit, its residual heat can be used to preheat air, water or another process fluid.

This is a problem encountered in steam-powered installations: heating coils, steam-to-water heat exchangers, industrial dryers and heat treatment equipment.

However, it is important to take action in the right place. Flash steam is not necessarily a fault: it occurs naturally when condensate that is hot enough moves from a high pressure to a lower pressure.

Why does flash steam form in a condensate system?

As it passes through a heat exchanger, the steam transfers its energy to the fluid to be heated and gradually condenses into water. However, the resulting water remains hot. It retains a significant amount of thermal energy and is still at a pressure determined by the operating conditions of the steam system. On leaving the equipment, the condensate may pass through a steam trap or be fed into a system operating at a lower pressure.

This is where the phenomenon may occur.

At atmospheric pressure, water boils at around 100 °C. At higher pressures, its boiling point increases. Consequently, condensates that were completely liquid at their initial pressure may become partially unstable when they enter a less pressurised system. A proportion of the water then immediately turns to vapour, without the need for any additional heat to be applied.

This vapour is known as flash vapour, or re-evaporation vapour.

It should not be confused with a leak of live steam. A visible plume following a pressure drop may result from the normal re-evaporation of hot condensate.

Why can a few kilograms of flash steam disrupt a network?

The problem stems in particular from the difference in volume between liquid water and steam. When a small proportion of the condensate re-evaporates, it can occupy a much larger volume than the original liquid.

Let us consider an order of magnitude: saturated condensate at around 7 bar relative pressure, when expanded to atmospheric pressure, can produce nearly 13 per cent flash vapour by mass. This proportion seems modest. However, the volume of vapour produced is considerable compared with that of the remaining water.

If the return pipe has not been designed to cope with this two-phase flow, a number of problems may arise: excessive velocity, increased back pressure, noise, reduced discharge capacity or operational instability.

In certain configurations, interactions between vapour pockets and condensate can also contribute to water hammer. The formation of flash vapour is therefore not necessarily abnormal. It is its occurrence in an unsuitable system that can become problematic.

Subcooling: recovering energy before the condensate re-evaporates

Le problème tient notamment à la différence de volume entre l’eau liquide et la vapeur. Lorsqu’une petite partie du condensat se réévapore, elle peut occuper un volume bien plus important que le liquide d’origine.

Let’s take an order of magnitude: saturated condensate at around 7 bar relative pressure, when expanded to atmospheric pressure, can produce nearly 13 per cent flash steam by mass.

This proportion may seem modest. However, the volume of vapour produced is considerable in relation to that of the remaining water. If the return pipe has not been designed to cope with this two-phase flow, a number of problems may arise: excessive velocity, increased back pressure, noise, reduced discharge capacity or operational instability.

Dans certaines configurations, les interactions entre les poches de vapeur et les condensats peuvent également contribuer à l’apparition d’un coup de bélier. La formation de vapeur instantanée n’est donc pas nécessairement anormale. C’est sa présence dans un système inadapté qui peut poser problème.

Subcooling: recovering energy before the condensate re-evaporates

One way of limiting flash vapour is to lower the temperature of the condensate before it reaches a lower pressure. This is the principle of sub-cooling.

Rather than allowing this energy to be lost into the return circuit, an additional heat exchanger enables it to be transferred to a cooler fluid.

In a steam-fired air heating system, for example, it is possible to organise heat recovery in two stages. The main heat exchanger receives the steam and provides the bulk of the air heating. The still-hot condensate then leaves this heat exchanger and passes through a second heat exchanger, where it transfers some of its energy to the incoming air.

Consequently, the air is preheated before reaching the steam coil, whilst the condensate emerges at a lower temperature.

This configuration offers two benefits: it utilises the residual heat contained in the condensate and reduces the risk of it re-evaporating when the pressure subsequently drops. However, a distinction must be made between sub-cooling carried out in a heat exchanger specifically designed for this purpose and the deliberate retention of condensate in a conventional steam coil.

Blocking the drainage of condensate to allow it to cool can flood part of the heat exchanger, impair performance and cause other operational problems. The recovery system must allow for drainage appropriate to the system’s pressure conditions.

Trianon Heat Exchanger project: condensate cooled from 170 °C to 57 °C

For an industrial paint-drying line, Trianon Échangeur designed a system aimed at heating a dry air stream from 30 °C to 80 °C, whilst improving energy recovery from the steam network.

The process utilised steam at 170 °C, with a stated operating pressure of 8 bar. After condensation, the water still retained a high temperature. It was necessary to recover this energy without causing unwanted re-evaporation in the return circuit.

The design office opted for a design incorporating two coils installed in series along the air path.

Condensate forms in the first steam coil; this hot condensate is then collected in the second heat exchanger to lower its temperature and prevent re-evaporation: at the same time, the energy from the condensate is recovered in the second heat exchanger

Cette organisation permet de valoriser successivement la chaleur de condensation de la vapeur, puis la chaleur sensible encore disponible dans les condensats.

How do you know what temperature to cool the condensate to?

The key factor is the minimum pressure that the condensate will encounter downstream of the equipment.

Each pressure corresponds to a saturation temperature. If the temperature of the condensate exceeds this temperature at the moment of expansion, some of the liquid may re-evaporate.

To ensure recovery without flash vapour formation at the location in question, the aim is therefore to achieve a condensate temperature below the saturation temperature corresponding to the downstream pressure, with a margin appropriate to the actual operating conditions.

For example, a return circuit operating at a pressure close to atmospheric pressure can accept water at 80 °C without causing it to boil simply by expanding at that pressure. By contrast, condensate at 170 °C expanded directly into the same circuit will produce flash steam.

This reasoning must be revisited if the pressure varies, particularly in the case of vacuum systems, significant pressure drops or transient operating conditions.

To size a subcooling heat exchanger, it is therefore necessary to know the condensate flow rate, its inlet temperature, its pressure and the conditions of the available refrigerant.

The power transferred can be estimated assuming the water remains in a liquid state and has a representative average heat capacity using the following equation:

P = ṁ × Cp × ΔT

Featuring:

  • P: recovered thermal power, in kW
  • ṁ: mass flow rate of condensate, in kg/s
  • Cp: average specific heat capacity of water, in kJ/(kg·K)
  • ΔT: différence de température des condensats entre l’entrée et la sortie de l’échangeur, en K.

Cette première estimation ne remplace pas le dimensionnement complet. Les pressions disponibles, les pertes de charge, les températures d’approche et les régimes transitoires doivent aussi être vérifiés.

Is it possible to prevent flash steam without cooling the condensate?

Subcooling is not the only solution.

Sur certaines installations, il est possible de conserver les condensats dans un réseau de retour pressurisé. Une pression plus élevée augmente leur température de saturation et peut limiter la fraction qui se revaporise. Cette solution doit cependant être étudiée avec prudence.

Increasing the back pressure in the return system may reduce the drainage capacity of the steam traps. If the pressure available in the heat exchanger becomes insufficient, condensate may accumulate there.

Le problème ne vient alors plus de la vapeur flash, mais du mauvais drainage de l’équipement.

C’est pourquoi le maintien en pression doit être envisagé à l’échelle du circuit vapeur, avec vérification des purgeurs, des dénivelés, des pompes éventuelles et des conditions de régulation.

Et si la vapeur flash est inévitable ?

It is not always necessary, nor is it economically viable, to eliminate all re-vapourisation. In some plants, flash steam can be recovered in an expansion tank and then used to meet a demand for steam at a lower pressure.

Other configurations allow this steam to be condensed in a heat exchanger so that its heat can be recovered. Where this is not possible, the system must, at the very least, be designed to cope effectively with the simultaneous presence of steam and condensate.

The right solution therefore depends on the objective: to prevent flash vapour from forming at a specific location, to recover its energy, or to control its discharge.

Mistakes that can make the problem worse

When a system exhibits steam plumes, unusual noises or difficulties with condensate return, it may be tempting to adjust the drain valves directly. However, a drain valve alone cannot prevent the re-evaporation of condensate whose temperature is too high for the downstream pressure.

Similarly, reducing the diameter of a pipe or altering its back pressure without carrying out a study risks simply shifting the problem elsewhere.

Another mistake is to seek a high degree of subcooling in a steam heat exchanger that is not designed to operate with a build-up of condensate.

The prolonged presence of water in the steam space may reduce the available condensation surface area and, depending on the installation, lead to problems with corrosion, control or water hammer.

Before making any changes, it is therefore necessary to distinguish between the phenomena observed:

  • Vapeur flash :revaporisation liée à la détente de condensats chauds.
  • Fuite de vapeur vive :passage anormal de vapeur, par exemple à travers un purgeur défectueux.
  • Inadequate condensate drainage: accumulation of liquid due to pressure, drainage issues or the operation of drain valves.
  • Cavitation :formation puis implosion de bulles de vapeur dans un liquide, notamment dans certaines conditions de pompage.

Ces phénomènes peuvent parfois coexister, mais ils n’appellent pas les mêmes corrections.

The benefits of a bespoke sub-cooling heat exchanger

Fitting a backup battery may seem relatively straightforward in theory. However, in an existing installation, the constraints are often greater.

A heat exchange surface must be found that is capable of cooling the condensate sufficiently, without causing excessive pressure drop or disrupting its discharge.

When heat is transferred to the process air, the heat exchanger must also fit within the available housing or duct, with an aerodynamic resistance compatible with the fans.

The design office can assist with the circuit layout, the selection of tubes and fins, the materials, and the arrangement of the two heat exchangers.

The paint-drying project is a prime example of this approach: sub-cooling was not treated as a separate operation, but as a stage integrated into the overall air heating process. This approach makes it possible to investigate steam coils and heat recovery coils suited to the thermal conditions and mechanical constraints of industrial installations.

Are you looking to minimise flash steam in your condensate system?

Does your plant use steam to heat air, water or another fluid, and would you like to recover more energy whilst managing the return of condensate?

An initial study can be carried out based on temperatures, pressures, the condensate flow rate and the heat demand that could utilise this heat.

Trianon Échangeur can assess the design of a sub-cooling coil or a thermal unit tailored to your process.

Contents

Live steam is produced by a boiler or a steam generator. Flash steam occurs when part of the hot condensate revervourises following a drop in pressure. The difference lies in how they are formed, not in their physical nature.

No, not on its own. A steam trap removes condensate from the steam system. When this condensate enters a system operating at a lower pressure, some of it may re-evaporate if its temperature is too high. Pre-subcooling or appropriate pressure control can reduce this phenomenon.

In a steam-fired air heating system, a first heat exchanger can preheat the air using the still-hot condensate, before a second heat exchanger, supplied with steam, provides the remaining heat. This cascade recovery makes better use of the energy in the steam circuit and can limit the re-evaporation of the condensate as it returns.

There is no universal temperature. It depends on the pressure in the return system. To prevent re-evaporation during a given pressure reduction, the condensate must be sufficiently cooled to remain in a liquid state at the downstream pressure.

Yes. A flash tank can be used to separate flash steam from liquid condensate so that the steam can be utilised at a lower pressure. It can also be condensed in a heat exchanger to recover its heat, provided that the installation conditions allow for this.