Our projects
How can condensate energy be recovered to optimise an industrial steam system?
In an industrial paint drying line, a significant proportion of the energy remains trapped in the condensate after condensation. Trianon Échangeur has designed a dual-coil system to recover this energy, eliminate the risk of flash steam and heat the air from 30 °C to 80 °C without excessive steam consumption.
Challenges: recovering energy from condensate without flash steam
In this type of system, a significant proportion of the energy remains in the condensate after condensation. The challenge was therefore to recover this energy whilst preventing flash vapour and ensuring that the condensate return was compatible with the steam loop.
Solution devised: a system comprising two batteries connected in series
We have designed a two-stage system based on two batteries connected in series:
- a condensate subcooling coil
- followed by a steam generator operating at 170 °C / 8 bar
How it works: cascade recovery
Specialised design: watertightness and mechanical strength
Two specific aspects of the project required a bespoke design:
- Ensure that each battery is watertight within the housing designed to accommodate them
- Increase mechanical strength by adding a 10 mm-thick backing plate and reinforcement brackets.
The system operates on a cascade recovery principle: the steam condenses in the main coil, and the still-hot condensate is then directed to the upstream coil. The heat from the condensate is transferred to the incoming air. The air is thus preheated before passing through the steam coil.
Temperature range: 170 °C to 57 °C, eliminating the risk of flash vapour
This principle makes it possible to reduce the temperature of the condensate from 170 °C to 57 °C, eliminate the risk of flash steam and make the most of the steam’s thermal capacity.
Materials and ASME U-STAMP certification
The design incorporates 304 stainless steel tubes and frames with aluminium fins for the condenser coil, whilst the evaporator coil is made entirely of 304 stainless steel to withstand higher temperatures. The design of both coils meets the requirements of the ASME U-STAMP code for installation in the United States.
Results: a compact, high-performance system
A compact, high-performance system capable of heating air from 30 °C to 80 °C whilst optimising heat recovery and managing process constraints.