Our achievements – Data centre

Adiabatic dry cooler heat exchanger for data centre cooling

Our projects

Adiabatic dry cooler heat exchanger

Data centre infrastructure requires highly reliable cooling systems to protect sensitive IT equipment.

TRIANON ÉCHANGEUR assisted a major player in the sector in improving the internal cleanliness of its heat exchangers, used in an adiabatic dry cooler cooling system.

The objective was to reduce impurities in the cooling system in order to protect sensitive components and ensure the performance of the installation.

A major challenge: internal cleanliness of heat exchangers

In data centre cooling systems, the presence of metal particles or oxidation residues can cause:

  • clogging of the hydraulic system

  • premature wear of sensitive components

  • a deterioration in thermal performance.

The project therefore consisted of designing a finned tube heat exchanger capable of limiting the risks of internal corrosion and metal contamination.

Design of a high-cleanliness finned tube coils

To meet the project requirements, we developed a specific solution for manufacturing heat exchangers.

Our technical choices have reduced potential sources of impurities in the cooling circuit.

The main improvements were:

  • brazing carried out in a controlled nitrogen atmosphere to limit oxidation residues

  • Stripping and passivation of manifolds in a bath to remove traces of oxidation and metal particles.

  • Implementation of a specific cleaning process with enhanced quality control.

A thorough inspection was even carried out using cotton buds to verify that there were no residues whatsoever in the internal circuits.

Prototype and industrial validation

In order to validate the technical choices, a prototype adiabatic dry cooler exchanger was built.

This prototype made it possible to:

  • validate manufacturing processes

  • test the internal cleanliness of the exchanger

  • confirm thermal performance under real-world conditions.

The results obtained enabled the launch of initial mass production to equip a new section of the Data Centre.

Production of 26 heat exchangers for 7.8 MW

Following validation of the prototype, an initial order was placed for the manufacture of 26 heat exchangers.

This equipment will provide a total cooling capacity of 7.8 MW for the Data Centre’s IT infrastructure.

This project illustrates TRIANON ÉCHANGEUR’s ability to develop specific technical solutions for environments with high energy requirements.

This project demonstrates the importance of tailor-made technical support in the design of heat exchangers for data centres.
Our teams have developed a specific production method, adapted to the customer's particular requirements and the technical constraints of the installation.

What are you looking for?