Our projects – Heat recovery from extracted air

Heat recovery from extracted air: over 650 kW recovered

Our projects

Récupération de chaleur à partir de l'air extrait : plus de 650 kW récupérés

How can we recover more than 650 kW from an extracted air flow whilst keeping pressure drops below 200 Pa?

For a heat recovery project in the HVAC sector, our engineering consultancy has designed an air-to-air plate heat exchanger intended to utilise a large volume of extracted air to heat an entrance hall.

The aim was to recover heat from exhaust air at 125 °C from a plant room, in order to preheat the outside air before it is blown into the hall. In winter conditions, the fresh air is assumed to be at -10 °C and must reach 50 °C at the heat exchanger outlet.

Heat recovery from extracted air to preheat fresh air

The high supply air temperature must meet a very specific operational requirement: to heat a hall with a ceiling height of over 5 metres.

Without a destratification system, it is therefore necessary to blow air at 50 °C to ensure an acceptable temperature at floor level.

The heat exchanger was designed in stainless steel, in accordance with the project requirements, to ensure long-term mechanical durability.

Each flow of 30,000 m³/h passes through a passage section measuring 1,600 x 1,600 mm, with a plate spacing of 13.5 mm.

Over 650 kW recovered with a pressure drop of less than 200 Pa

This design choice makes it possible to achieve the target thermal output, in excess of 650 kW, whilst limiting the air pressure drop to less than 200 Pa.

A key factor in maintaining the existing ventilation system and facilitating the integration of the equipment into the installation.

The combination of high power, a stainless steel design and the spacing between the plates requires a large heat exchange surface area. The heat exchanger therefore weighs around 800 kg, reflecting its robust design, which is sized to withstand demanding thermal, mechanical and aerodynamic stresses.

This project demonstrates our ability to design bespoke heat exchangers for heat recovery applications involving extracted air, taking into account performance, integration and operational requirements right from the design stage.

A project to recover heat from extracted air? Do you have a project involving heat recovery from extracted air, or a specific requirement for an air-to-air heat exchanger? Nos équipes vous accompagnent dans la conception d’une solution adaptée à vos contraintes.

What are you looking for?