Bespoke, adaptable & versatile – Our glycol filled water coil
Glycol-filled water coil
Our glycol filled water coil
Batterie à eau glycolée sur mesure pour le refroidissement industriel
La batterie à eau glycolée est un échangeur thermique à tubes et ailettes conçu pour assurer le transfert de chaleur entre un circuit d’eau glycolée et un flux d’air.
Suitable for industrial installations requiring protection against freezing or operation at low temperatures, it cools the air whilst meeting thermal, hydraulic and integration requirements.
Trianon Échangeur designs and sizes bespoke glycol-water heat exchanger coils, taking into account the glycol concentration, operating temperatures, flow rates and permissible pressure drops.
Glycol-filled water coil
Technical specifications
Tubes diameters
4 mm
5 mm
5/16” (7,94 mm)
3/8” (9,52 mm)
1/2” (12,4 mm)
5/8” (16,4 mm)
7/8” (21,9 mm)
Materials
tubes: copper (smooth or finned) – tinned copper – cupro – nickel – stainless steel aisi 304l & 316l – 316ti
fins: aluminum – pre-painted aluminum – almg – copper – tinned copper – stainless steel aisi 304l & 316l – 316ti
Geometries
P20x17
P25x12 l P25x22 I P25x50
P30x26 I P30x30
P32x28
P37x32
P40x35
P48x42
P50x50
P60x30 I P60x60
Manufacturing & Application
Finned coil
Fin thickness: 0.1 to 0.4 mm
Fin pitch: 1.6 to 12 mm
Tube diameter: 4 to 22 mm
Surface treatments: Hérésite, Epoxy,
Cataphoresis, Blygold…
Curved coils
Bespoke copper or stainless steel manifolds.
All sizes up to 12 ml
Leak testing of our coils under pressure at 30 bar (150 bar for CO₂ testing)
Water, glycol-water mixtures, refrigerants (R513A, R410A, etc.), NH₃, CO₂, other fluids...
Options
- custom frame drilling
- defrost heater
- anti-corrosion treatment
- dampers
Standards
Quality System: UNI EN ISO 9001:2008
Performance: AHRI & HTRI
DESP 2014/68/EU (up to Cat. IV)
Manufacturing codes: EN 13445-3 / ASME VIII Div. 1
Brazing in accordance with EN 1334 / EN 13133
Welding in accordance with EN 288 / EN 15614-6 / EN 15613 / EN 287-1 / EN 9606-3 or ASME IX
Visual and non-destructive testing: UNI EN 9712:2012 & SNT-TC-1A Ed. 2006
Zoom sur les industries et applications des batteries eau glycolée
Domains
Industrial refrigeration
HVAC
Commercial refrigeration
AHU
Heat Pump
Food Industry
Set up your glycol-water battery
To obtain a detailed quotation, a telephone appointment with one of our sales representatives will be scheduled. Please note that this configurator is a tool managed by an algorithm and does not serve as a personalized technical study. For further information, please contact us via the online form.