FAQ – Heat exchangers
How do you size a heat exchanger?
How do you size a heat exchanger?
The design of a heat exchanger involves defining a solution capable of transferring thermal power between two fluids under specific operating conditions. It is not simply a matter of selecting equipment based on its dimensions: it is necessary to analyse the fluids, temperatures, flow rates, pressure, pressure drops, space requirements, materials, the environment and maintenance requirements.
In industry, an air-to-water, air-to-steam, air-to-flue gas or air-to-air heat exchanger, a finned coil or a heat recovery unit are not subject to the same constraints. Each application has its own specific parameters: inlet temperature, outlet temperature, nature of the fluids, operating pressure, risk of fouling, corrosion, integration into an existing system or replacement with an identical unit.
Trianon Échangeur designs bespoke heat exchangers based on the project’s technical specifications. The aim is to provide a solution that is consistent with the expected performance, installation constraints and actual operating conditions.
Why is the sizing of a heat exchanger important?
An incorrectly sized heat exchanger can lead to a loss of performance, higher energy consumption, excessive pressure drops or premature wear and tear on the system.
An undersized heat exchanger may not achieve the required thermal output. An oversized heat exchanger may be more expensive, take up more space and, in some cases, be less suited to actual operating conditions.
Sizing therefore enables us to strike the right balance between:
- the thermal power to be transferred
- la surface d’échange nécessaire
- permissible pressure drops
- the available space
- the materials
- ease of maintenance
- resistance to fouling
- corrosion resistance
- integration into the existing system
This stage is particularly important for industrial heat exchangers, finned heat exchanger banks, heat recovery units and like-for-like replacements.
What data is required to size a heat exchanger?
To carry out a design study, a number of details are required. The more accurate the data provided, the more reliable the technical analysis will be.
The main details to be provided are:
- the nature of fluids
- air or fluid flow rates
- inlet temperatures
- the desired outlet temperatures
- the expected thermal output
- the maximum design pressure and temperature (PS/TS)
- permissible pressure drops
- the installation environment
- the available space
- connection constraints
- the risk of clogging
- the risks of corrosion
- cleaning requirements
- the materials requested or specified
- specific standards or requirements
When replacing a heat exchanger, it is also helpful to provide a diagram, photographs, an existing part number or a set of measurements. These details enable the mechanical integration of the old equipment to be maintained whilst ensuring the required thermal performance is met.
The physical principles of thermal calculation
A heat exchanger relies primarily on two phenomena: convection and conduction.
Convection refers to the transfer of heat between a moving fluid and a wall. In industrial applications, this convection is often forced: air circulation by a fan, water circulation by a pump, or the circulation of steam, fumes or process fluids.
Conduction refers to the transfer of heat through the wall of the heat exchanger: a tube, plate, fin or metal surface. The material used therefore has a direct influence on the quality of the heat transfer.
Radiation may play a role in certain high-temperature applications, but it is often a secondary factor in standard calculations for industrial heat exchangers.
Dimensioning involves matching three elements:
- the thermal power to be transferred
- the available heat transfer surface area
- the actual conditions under which fluids flow
Calculating the thermal capacity of a heat exchanger
Thermal power is the amount of energy that the heat exchanger must transfer between two fluids.
In a simple case, it can be estimated using the formula:
P = ṁ x Cp x ΔT
with :
- P : thermal power in W or kW
- ṁ : mass flow rate of the fluid in kg/s
- Cp : specific heat capacity of the fluid in J/kg·K
- ΔT : temperature difference between the fluid inlet and outlet, in K or °C
When the flow rate is expressed as a volumetric flow rate, the following can be used:
P = ρ x Qv x Cp x ΔT
with :
- ρ : density of the fluid in kg/m³
- Qv : volume flow rate in m³/s
- Cp : specific heat capacity
- ΔT : temperature difference
These formulas provide an initial estimate of the power to be transferred. However, they are not sufficient for the complete sizing of an industrial heat exchanger. The design team must then take into account the technology, pressure drops, heat transfer surface area, materials, fouling and operating constraints.
Choosing the right heat exchanger technology
Before finalising the calculation, you must select the heat exchanger technology best suited to your requirements.
An air-to-water heat exchanger is used to heat or cool a flow of air using hot water, chilled water or glycol-based water. It is commonly used in air handling units, industrial installations and finned coils.
An air/steam heat exchanger uses steam as the hot fluid. It is suitable for applications requiring high thermal output or a rapid rise in temperature.
An air/flue gas heat exchanger is used to recover the energy contained in industrial flue gases. It must be sized taking into account the temperature and humidity of the flue gases in order to control condensation, as well as their composition, fouling, corrosion and maintenance requirements.
An air-to-air heat exchanger transfers heat between two air streams without them mixing directly. It can be used in energy recovery or air treatment projects.
A finned tube coil is used to heat, cool or recover thermal energy from an air flow.
Its dimensions depend mainly on several factors:
- The geometry of the heat exchanger: centre-to-centre distance between tubes, length and height
- The pitch of the blades
- The number of rows of tubes
- Materials used: tubes, fins and frame
- Operating conditions: flow rates, inlet and outlet temperatures
The choice of technology has a direct impact on the heat transfer surface area, pressure drops, space requirements and maintenance.
Calculate the average temperature difference
When sizing the heat transfer surface area, it is not enough simply to consider the temperature difference at the inlet or outlet. The temperature difference between the two fluids changes along the length of the heat exchanger.
We therefore use the mean logarithmic temperature difference, known as DTLM or ΔTLM.
The formula is:
ΔTLM = (ΔT1 – ΔT2) / ln(ΔT1 / ΔT2)
with :
- ΔT1 : temperature difference between the two fluids at one end of the heat exchanger
- ΔT2 : temperature difference between the two fluids at the other end
- ln : natural logarithm
The DTLM provides an average difference that is representative of the actual heat transfer. It is used to estimate the required heat transfer surface area.
Please note: this approach must be adapted to suit the heat exchanger’s configuration, the direction of fluid flow, any changes of state and the actual operating conditions.
Determine the heat transfer area
Once the thermal power and the DTLM are known, the required heat transfer area can be estimated.
The basic relationship is:
P = K x S x ΔTLM
with :
- P : heat exchange capacity
- K : overall heat transfer coefficient
- S : exchange surface
- ΔTLM : mean logarithmic temperature difference
The exchange surface can therefore be expressed as follows:
S = P / (K x ΔTLM)
This formula helps us to understand the relationship between power, heat transfer surface area and the quality of heat transfer.
In practice, the heat transfer area depends on the technology used: tubes, fins, plates, bundles, the number of rows, tube length, diameter, frontal area, flow velocity and the geometry of the heat exchanger.
For a finned heat exchanger, for example, the heat transfer surface area depends on the number of fins, the fin pitch, the tube diameter, the number of rows and the air flow.
Understanding the overall heat transfer coefficient
The overall heat transfer coefficient, often denoted by K or U, represents the heat exchanger’s ability to transfer heat between two fluids
It depends, in particular, on:
- convection coefficients on the hot-fluid side and on the cold-fluid side
- the thermal conductivity of the wall
- the wall thickness
- the materials used
- traffic speeds
- the geometry of the heat exchanger
- of the flow regime
- clogging
- of the surface finish
A simplified expression for the overall thermal resistance can be written as follows:
1 / K = 1 / h1 + e / λ + 1 / h2 + Rf
with :
- h1 : convective heat transfer coefficient on fluid side 1
- h2 : convective heat transfer coefficient on fluid side 2
- e : wall thickness
- λ : thermal conductivity of the material
- Rf : fouling-induced resistance
This formula provides a simplified view. In industrial design, the actual calculation of the overall heat transfer coefficient depends on numerous parameters: the physical properties of the fluids, flow velocities, geometry, materials, fouling conditions and operating constraints.
Internal calculation and selection methods are therefore not limited to a single formula. They require a comprehensive technical analysis.
Check for pressure drops
Pressure drops correspond to the resistance encountered by fluids as they flow through the heat exchanger. They are expressed as a pressure difference.
They may come from:
- friction along the walls
- changes in direction
- connections
- changes in cross-section
- flow through the fins
- internal geometry
- due to gradual build-up of dirt
A general formula used in fluid mechanics is:
ΔP = f x (L / D) x (ρ x v² / 2) + Σζ x (ρ x v² / 2)
with :
- ΔP : pressure drop
- f : coefficient of friction
- L : passage length
- D : hydraulic diameter
- ρ : density of the fluid
- v : fluid velocity
- Σζ : sum of the singular loss coefficients
This formula provides a basis for understanding. In a heat exchanger, the actual pressure drops depend on the technology, the geometry, the flow velocities, the fluids and the degree of fouling taken into account.
This step is essential, particularly in projects involving a like-for-like replacement. The new heat exchanger must remain compatible with the existing fans, pumps, ducts, and hydraulic or steam systems.
Take fouling into account
Fouling creates additional resistance to heat transfer. It can reduce the heat exchanger’s performance, increase pressure drops and lead to more frequent maintenance.
The risk of fouling depends, in particular, on:
- the nature of fluids
- the presence of dust or particles
- water quality
- the presence of condensate
- fumes
- contaminated fluids
- temperature
- of the feed rate
- from accessibility to cleaning
In a finned coil, the fin pitch is an important parameter. A pitch that is too narrow may encourage the build-up of dust in a dusty environment. A wider pitch may make cleaning easier and limit the increase in pressure drop over time.
Fouling must therefore be taken into account right from the design stage, without waiting for the first signs of a decline in performance.
Incorporating corrosion and surface treatments
In certain environments, corrosion can significantly reduce the service life of a heat exchanger. This is the case in humid, saline or chemical environments, or where the fluids are corrosive.
The choice of materials and surface treatments must therefore be carefully considered.
According to the project, several parameters can be analysed:
- nature of the fluids
- operating temperature
- humidity
- presence of chemical agents
- outdoor exhibition
- presence of salt air
- cleaning frequency
- maintenance requirements
- expected lifespan
A surface treatment may be considered to improve corrosion resistance, but it must remain compatible with the expected temperatures, materials, mechanical stresses and thermal performance.
Is it possible to size a heat exchanger without all the data?
An initial analysis can be carried out using partial data, but a reliable design requires a minimum amount of technical information.
The priority data are:
- fluids
- flow rates
- the inlet and outlet temperatures
- operating pressure
- the required power
- permissible pressure drops
- the installation environment
- the available space
In the case of a replacement, a diagram, photographs, an old heat exchanger or a set of measurements may help to reconstruct the mechanical constraints. However, operating data is still required to validate the thermal performance.
Trianon Échangeur supports manufacturers, installers, operators and engineering firms in the calculation and design of bespoke heat exchangers.
The design office analyses the project data to devise a suitable solution:
- fin-type heat exchanger
- Hot water coil
- cold battery
- steam generator
- air-to-water heat exchanger
- air-vapour heat exchanger
- air-to-flue gas heat exchanger
- air-to-air heat exchanger
- Heat recovery unit
- replacement heat exchanger
- industrial heat recovery solution
The study takes into account thermal performance, pressure drops, materials, space constraints, connections, the environment, fouling, corrosion and maintenance.
The aim is to propose a heat exchanger that is consistent with the existing installation, the energy performance targets and the actual operating conditions.
Need to size a heat exchanger?
The basic formula is P = ṁ × Cp × ΔT. It relates thermal power to the mass flow rate, the specific heat capacity of the fluid and the temperature difference. It provides an initial estimate, but industrial design work then requires verification of the heat transfer surface area, pressure drops, materials and operating constraints.
The DTLM, or average logarithmic temperature difference, is used to assess the average temperature difference between the two fluids over the entire length of the heat exchanger. It is used to estimate the required heat transfer area.
Pressure drops affect the operation of pumps, fans and associated systems. If they are too high, they can reduce flow rate, increase energy consumption and impair the system’s performance.
Yes. Fouling must be taken into account right from the design stage, as it can reduce heat transfer and increase pressure drops. It can influence the choice of fin pitch, materials, surface treatment and ease of cleaning.
Yes. A like-for-like replacement can retain the dimensions, connections and installation constraints of the old heat exchanger, whilst allowing the thermal performance to be checked or adjusted in line with current operating conditions.