Our projects – Sawmill heat exchanger

Heat exchanger for a sawmill: 1.2 MW on the roof with less than 50 Pa

Our projects

Échangeur de chaleur pour une scierie : 1,2 MW sur le toit avec une pression inférieure à 50 Pa

The challenge: to design a heat exchanger for a sawmill, intended for drying timber, to be installed on the roof, handling air with 65 per cent humidity at 30 °C, with a total capacity of 1.2 MW across two coils and a pressure drop of less than 50 Pa.

For a sawmill specialising in the drying of timber for pellet production, our engineering department designed finned-tube heating coils, integrated into the roof of a drying tunnel, whilst optimising the existing equipment.

The aim was to generate the hot air required for the process by heating 30,000 m³/h of air at 30 °C – 65 per cent RH – to 90 °C, using a hot water loop at 95 °C.

A heat exchanger designed to cope with the demands of the sawmill

The main constraint was that the batteries had to retain their existing dimensions, drilling positions, flange layout and flow cross-section.

Measuring over 4 metres in length and less than 1.5 metres in height, weight also became a key consideration, particularly for flat-roof installation.

The choice of materials was tailored to the environment: copper tubes, aluminium fins and a galvanised steel frame, as there was no specific risk of corrosion.

This combination optimises the thermal performance-to-weight ratio, which is an important consideration for rooftop installations.

A design optimised for wood drying

The airflow pattern also influenced the design. Air flows through the coils vertically, from the outside inwards, which minimises dust being blown onto the heat exchange surface.

This low risk of fouling has enabled us to optimise the geometry, reducing the spacing between rows and tubes from 35 mm to 30 mm, and lowering the fin pitch to 2.5 mm.

620 kW per battery with less than 50 Pa of pressure drop

Each battery unit delivers a power output of around 620 kW, with a heat exchange surface area of nearly 600 m², whilst keeping the weight below 400 kg.

This optimisation reduces the number of rows and keeps the air pressure drop below 50 Pa.

On the hydraulic side, the circuit layout has also been optimised, with 100 connections per manifold, in order to limit pressure drops to around 20 kPa per battery.

This project illustrates our bespoke approach: tailoring the thermal, air-handling, hydraulic and mechanical design to the actual constraints of the process and the existing installation.

The design of this heat exchanger for sawmills therefore meets several simultaneous requirements: high thermal output, low pressure drop, weight control, integration into the roof structure, and operation in an environment dedicated to timber drying.

A heat exchanger project for a sawmill?

Do you have a project involving industrial drying, battery replacement or integration into an existing production line?

Our design office can assist you in designing bespoke heat exchangers for sawmills and industrial plants, tailored to the specific requirements of your process.