What is the difference between a sensible heat recovery unit and a condensing heat recovery unit?

A sensible heat exchanger transfers energy resulting from the temperature difference between two fluids, without deliberately utilising any change in their state.

A condensing heat recovery unit goes one step further: it cools a moist fluid until some of its water vapour condenses, thereby also recovering the energy associated with the change of state: latent heat.

This distinction can significantly alter a plant’s energy balance. In exhaust air from a dryer, boiler flue gases or certain industrial emissions with high moisture content, water vapour carries energy that is not apparent when considering temperatures alone.

However, systematically seeking to recover condensate is not always justified from an energy or technical perspective. Whether it is worthwhile depends, in particular, on the humidity of the extracted air, the temperature of the fluid to be heated, and the amount of recoverable latent heat. The risks of corrosion, condensate management and maintenance requirements must also be taken into account in order to ensure a favourable overall energy balance.

Sensible heat and latent heat: what are we actually recovering?

Let us consider a stream of hot air passing through a heat exchanger to preheat fresh air. As long as the first fluid cools without its water vapour condensing, the energy transferred corresponds mainly to its sensible heat. Its temperature decreases, but the water present in the form of vapour remains in the same state.

If cooling continues and the conditions for condensation are met (dew point), some of this water vapour turns into liquid. This change of state releases additional energy: the latent heat of condensation. The heat exchanger can then transfer two sources of heat to the cold fluid: the energy associated with the cooling of the gas and that released by the condensation of the water.

It is this second contribution that distinguishes condensing recovery from purely sensible recovery.

Why can condensation provide more energy?

The evaporation of water requires a significant amount of energy. When this vapour returns to its liquid state, it releases some of that energy.

As a rough guide, the condensation of one kilogram of water vapour releases approximately 2,300 to 2,500 kJ of latent heat, depending on its temperature and the thermodynamic conditions.

In a process that releases several tens of kilograms of water vapour per hour, this contribution can become significant. However, a distinction must be made between the energy that is theoretically available and that which is actually transferred. It all depends on the amount of water that condenses, the temperatures involved, and the capacity of the cooling circuit to absorb this heat.

The dew point: the boundary between the two modes of operation

To determine whether a heat recovery unit can operate under condensation conditions, you need to know the dew point of the hot gas stream.

This is the temperature at which water vapour begins to condense, for a given pressure and composition.

In a humid industrial environment, this factor depends in particular on the steam’s water content and pressure. Two streams leaving at the same temperature may therefore behave very differently within a heat exchanger.

Relatively dry air can be cooled significantly without producing condensation. Very humid air may start to condense much earlier.

One technical detail is also worth highlighting: condensation occurs when gas comes into contact with surfaces if their temperature is low enough. It can therefore occur locally on plates or tubes, even if the average temperature of the gas remains above its dew point.

It is not just the outlet temperature of the heat exchanger that matters, but also the actual temperature of the heat exchange surfaces.

When it comes to industrial flue gases, the analysis becomes even more complex. Certain compounds present in the gases can form acidic condensates, sometimes at temperatures different from the dew point of water. It is therefore necessary to assess the risk of corrosion before attempting to cool the flue gases further.

Sensitive heat recovery units or those with condensation: the key differences

Sensitive recovery Recovery with condensation Heat associated with the cooling of the fluid Sensible heat and latent heat Desired change of state No

Yes, condensation of water vapour Air, gas, fumes or other hot fluids Air or gas containing sufficient moisture Primarily thermal and air-flow or hydraulic Thermal, air-flow or hydraulic, including a moisture analysis and suitable materials Normally avoided or not sought after Expected and to be collected Performance, pressure drops, fouling As well as drainage, corrosion and maintenance of wetted surfaces
Criterion
Recovered energy
Relevant fluids
Sizing
Condensate
Areas to monitor

These are not two technologies that are necessarily at odds with one another. A single heat exchanger can transfer both sensible heat and latent heat, provided that its operation results in condensation and that it is designed for this purpose.

The difference therefore lies as much in the thermal conditions as in the way the equipment has been sized.

Why is a condensing heat recovery unit not sized in the same way as a sensible heat recovery unit?

For a fluid undergoing no change of state, an initial estimate of the power exchanged can be made using the mass flow rate, the specific heat capacity and the temperature difference: P = m Cp ΔT (where m is in kg/s, Cp is in kJ/kg·K, ΔT is in K and P is in kW)

When water vapour condenses, this calculation is no longer sufficient. One must take into account the change in the enthalpy of the moist air or flue gases and the quantity of water that changes to a liquid state, and the calculation becomes

P = m Δh (where m is in kg/s, h in kJ/kg and P in kW)

For an air-to-air heat exchanger, the parameters to be analysed include, in particular, the dry air flow rate, temperature, absolute humidity and the outlet conditions of the two circuits.

We need to determine the expected condensate flow rate and check how it varies under different operating conditions.

This is particularly important for installations subject to seasonal variations or changes in production. A heat recovery unit may operate without condensation under certain conditions and produce a significant amount of water under others.

The design of the heat exchanger must allow water to drain away

A condensing heat recovery unit must not allow water to accumulate on its surfaces.

In a plate heat exchanger, the spacing between the plates, the orientation and the flow pattern must allow the condensate to be drained off without causing excessive stagnation. In a tube bundle heat exchanger, the arrangement of the tube bundle, the water recovery system and the drainage arrangements must be appropriate.

In both cases, the presence of condensate can affect pressure drops and heat transfer. A collection and drainage system (condensate tray) must therefore be provided where condensation is likely to occur in the system.

The choice of materials is becoming more important

Where the fluid is clean and non-corrosive, certain aluminium or galvanised steel structures may be suitable for the conditions specified for the project.

Where fumes or chemical effluents are present, the choice may be quite different. Condensate may concentrate or dissolve compounds that are corrosive to heat exchange surfaces. The use of stainless steel, compatible plastics or special treatments may then be considered.

The material must be selected according to the actual composition of the fluid and the condensate. 316L stainless steel, for example, is not resistant to all corrosive conditions.

Accessibility for cleaning deserves the same attention. A wet heat exchanger that is difficult to inspect or exposed to deposits can quickly lose some of its performance.

Trianon Heat Exchanger project: 57 litres of condensate per hour from an air-to-air heat recovery unit

Latent heat recovery can be a key factor in the design of a heat exchanger.

This is illustrated by a project carried out by Trianon Échangeur for a catalyst production line.

The aim was to recover heat from a highly humid stream of hot air, originating from a desiccant wheel, in order to preheat the air entering an industrial dryer.

The difficulty lay not only in the power to be transferred. The cooling of the wet flow was expected to result in significant condensation, which had to be taken into account in the design of the heat exchanger.

Les caractéristiques du projet :

  • Preheated air from 20 °C to 82 °C;
  • Claimed wet efficiency: 95 per cent;
  • Estimated condensation: approximately 57 litres of water per hour;
  • Pressure drops of less than 100 Pa;
  • Air-to-air heat exchanger with aluminium plates, fitted with a galvanised steel frame.

In particular, the design team worked on the spacing of the plates to allow condensate to drain away and prevent it from accumulating in the heat exchanger.

The condensate flow rate was assessed for various operating conditions. The heat exchanger had to provide the required preheating whilst also remaining compatible with the installation’s space requirements and airflow constraints. The materials were selected on the basis of the nature of the fluids, which were characterised in this project as non-corrosive and non-fouling.

The value of this project lies in demonstrating that condensation can be a genuine source of thermal performance, provided it is incorporated into the calculations and design from the outset.

It should also be noted that the 95 per cent wet efficiency corresponds to the conditions and indicator used for this project. It does not mean that all condensing heat recovery units achieve this level of performance.

In which situations should one opt for sensible heat recovery or condensing heat recovery?

A sensitive heat recovery unit may be a suitable solution where the hot fluid contains little moisture, where the heating requirement does not necessitate significant cooling, or where condensation needs to be avoided.

This is particularly the case for many applications involving the preheating of fresh air, ventilation or heat recovery from flue gases, where the operating conditions allow heat exchange to take place without the formation of condensate.

Condensation-based heat recovery becomes particularly advantageous when three conditions are met:

  • The hot fluid contains sufficient water vapour
  • Le second fluide suffisamment froidpermet d’atteindre les conditions de condensation
  • l’énergie récupérée peut être utilisée par le procédé ou un autre équipement.

The humid exhaust air from certain dryers, boiler flue gases and industrial installations producing large volumes of water vapour may be of interest.

It is, however, necessary to check that condensation can be controlled from a technical point of view. An additional heat gain does not justify a design that would promote corrosion, fouling or operational problems.

What if the circuit to be heated isn’t cold enough?

This is a limitation frequently encountered in heat recovery projects involving condensation.

If the cold fluid arrives at too high a temperature, the heat recovery unit may not be able to achieve the conditions required to condense a significant amount of water vapour. A larger heat exchanger will not necessarily solve this problem.

In some projects, the use of a low-temperature water circuit or the incorporation of a heat pump may allow for greater efficiency. However, this solution must be assessed in the context of the entire installation and its overall energy balance.

How Trianon Échangeur designs its heat recovery units for these two operating modes

Trianon Échangeur offers a range of heat recovery technologies which can be assessed depending on the hot fluid and the energy to be recovered.

Air-to-air plate heat exchangers enable energy to be transferred between two gas streams. In applications where condensation is expected, the geometry, materials and water drainage must be appropriate.

Finned-tube heat exchangers can be used to transfer heat from air or flue gases to a fluid. Their design may incorporate smooth or finned tubes, a variety of materials, and condensate collection systems.

In flue gas applications, corrosion and the composition of the emissions may influence the choice of a specific design.

The challenge for the design office is not to treat humidity as a mere secondary parameter. Where it affects the recoverable heat output, it must be taken into account in the thermal calculations and in the design decisions.

It is also important to distinguish between condensation-type heat recovery units and membrane-type heat recovery units with moisture transfer. The latter facilitate the exchange of heat and water vapour through a membrane, depending on their design. They do not necessarily rely on the collection of liquid condensate and serve other purposes, particularly in air treatment.

Would you like to recover heat from a stream of humid air or industrial fumes?

Does your plant discharge hot air containing moisture, fumes or process gases?

To assess the potential for heat recovery, the first pieces of useful information are the flow rates, temperatures, humidity and composition of the flow, as well as the characteristics of the fluid you wish to heat.

These data make it possible to assess whether significant recovery is sufficient or whether condensation may offer additional benefits.

Trianon Échangeur designs and sizes bespoke heat recovery units, taking into account the actual behaviour of the flow patterns and the installation constraints.

Contents

Yes. If the heat exchange surfaces reach a temperature below the dew point of the moist fluid, condensation may occur even if this was not intended. It is therefore necessary to check the operating conditions and put the necessary protective measures in place.

It can recover more energy by utilising latent heat, but this depends on the humidity of the air stream and the temperature available on the cold side. The energy savings must also be weighed against the constraints relating to design, maintenance and operation.

Sensible efficiency characterises temperature-based heat recovery, according to a given calculation definition. Humid efficiency may take into account the effects of condensation and latent heat. These indicators are not directly interchangeable: one must be familiar with their definitions and reference conditions in order to compare two heat recovery units.

When an industrial gas is cooled, certain compounds may dissolve in the condensed water or form acidic condensates. Depending on their nature and concentration, they may corrode metal surfaces. The choice of materials must therefore take into account the composition of the gases and any liquids that may form.

An air-to-air heat recovery unit or an air-to-liquid heat exchanger can be designed according to the intended use of the heat. If the humid flow is cooled to the point of condensation, the design must take into account the latent heat, the condensate flow rate, the materials used and their drainage.